Tech data of 10kv, 11kv SC(B)10 series resin insulation dry-type power transformer

1. Standards: GB1094-1996; JB/T10088-2004; GB/T10228-2008; EQV IEC726
2. Voltage Grade: 6, 10, 6.3KV, 11kV
3. Voltage Regukation Mode: Off circuit tap changing; On load tap changing
4. Tapping Range: ± 5%, ± 2× 2.5%, ± 4× 2.5% or others
5. Frequency: 50Hz; 60Hz
6. Phase: Three phase
7. Connection Sign: Yyn0, Dyn11 or others
8. Short Circuit Impedance: Standard impedance (For details see technical data sheet)
9. Max. Temperature: 120K
10. Cooling Method: ONAN or ONAF
11. Insulation Class: Grade F

Features:
High voltage coils are wrapped with Polyester enameled wires, filled with glass fiber, and then resin under vacuum condition. It becomes solid under high temperature. It equipped with high mechanical intensity, low discharge partly; Low voltage coils are wrapped with a whole piece of copper foil, with strong anti-shortcut capacity. The core is made of silicon steel. By reasonable choosing magnetic density, decrease the empty loading loss effectively
Fire protection, anti-explosion, and no pollution
Coil is free from humidity, low noise and well characteristic of heating dispersion
Low loss, energy saving, free from maintenance, small size, light, and easy for installation
Technical Data of 10kV  SCB(10) Cast Resin F Insulation Class Dry Type Power Transformer 
   Loss(kW) Insulation LevelWeight (kg)Outline Dimension (mm)Outline dimension with protective casing
Rated CapacityVoltage Group(kV)Connection Method   (120C)No-load current  (L)(W)(H)(L)(W)(H)
(kVA)HVLVNo-loadLoad%     
10   0.1350.3054 130600450490900800850
20   0.170.5953.5 170600450560900800850
30   0.1950.7052.6 33062045065010509001000
50   0.270.9952.2 38062045075010509001000
63   0.331.212.2 440750500760105010001150
80   0.371.382.2 510750500760110010001150
100   0.41.572 590750500890115011001250
12511 Dyn110.471.851.8 65010606001020135010501200
16010.50.4 0.5452.131.8F/F78010606001060140010501250
20010 Yyn00.6252.531.6 93010607101120145011001350
2506.3  0.722.761.6 104011007101140150011501400
3156  0.883.471.4 118011507101195150012001450
400   0.9753.991.4 145012608701285160012501600
500   1.164.881.4 163012908701355160013001650
630   1.3455.871.2 190014508701420180013001700
630   1.35.961.2 190015008701370185013001650
800   1.526.9551.2 229015508701570190013001800
1000   1.778.131.1 270016008701665195013001950
1250   2.099.691.1 3130168011201765205013502000
1600   2.4511.731.1 3740175011201860210014002100
2000   3.3214.451 4150177011201865215015002100
2500   417.171 4810187011201950220015002200
3150   5.1422.50.8 5800195011201900235016002250
4000   5.96270.8 7100210011202050240016002300
(Note): (Tapping range of high voltage) ± 5%; ± 2× 2.5%, Frequency: 50Hz. 